DTZY150-Z three phase four wires remote fee control smart electric meter is a intelligent electric metering product which made of large scale integrated circuit, with Digital sampling processing technology and SMT craft.
It is compatible with IEC 62053-21 <Part 21L Static meters for active energy classes 1 and 2>,and meet with DL/T645–2007 <Multi function static meter communication protocol> requirements.
Main Features:
● Metering
● Tariff
● Loadprofile
At least 4 loadprofile channels,Recordat least 490days data when time interval is 30 minutes
● Remote ON/OFF Control
Remote ON/OFF control through background software, senior password authorization needed.
● Optical port interface
Support IEC62056-21protocol, 1200bps for communication
● RS-485 serial interface
SupportIEC62056(DLMS/COSEM) protocol, 2400bps for communication
● LCD display
Number of digits value field Up to 8
Digit size 6x14.5mm
● Inputs and outputs
Optical test outputs active energy and reactive energy
● Communication modules(optional)
GPRS module:EGSM900/DCS1800 dual-band,support GSM/GPRSphase2/2+ protocol
PLC module: according to Technology Standards of SSC163X ,centerfrequency 270K, FSK modulate technolgy
● Energy Measurement
Total and time-sharing forward active & reactiveenergy measurement
Total and time-sharing reverse active & reactive energymeasurement
Total forward & reverse apparent energy measurement
Save last one to sixteen months energy data
● Max. Demand Measurement
Measure total and time-sharing forward active &reactive maximum demand and time of occurred
Measure total and time-sharing reverse active &reactive maximum demand and time of occurred
Measure total forward & reverse apparent maximumdemand and time of occurred
● Real Time Measurement
Real-time measurement of the phase voltage, current,total active power,
reactive power, apparent power, total power factor, powergrid frequency
● TOU
4tariffs, 100holidays, 14season‐tables, 8time zone‐tables, each table onmaximum 14 time zones
● Event Log
The last 10 records of following events:Power-down,Programing, Cover opening, Terminal cover opening, Reverse power,
PhaseFail.the records include data and time
Main Parameter:
Item | Specification | |
Reference Current | 1.5(6)A 5(40)A 5(60)A 15(60)A 20(100)A | |
Reference Voltage | 3×220V/380V | |
Dimension (mm) | 290×170×85 | |
Working Voltage Range | 0.8Un~1.15Un | |
Maximum Working Voltage | 0.7Un~1.2Un | |
Temperatura de trabajo | -25℃~+60℃ | |
Temperatura de trabajo máxima | -40℃~+70℃ | |
Accuracy | Active 1.0 | 2,0 reactivos |
Humedad relativa | el ≤95% | ||||||
Frecuencia | (45~60) herzios | ||||||
Presente del comienzo | Modo directo los 0.004In; | ||||||
Modo del CT: los 0.002In | |||||||
Consumo | <1.5W, 10VA |
Ajuste de la fábrica conforme al letrero | ||||||||
Para 1.5(6) al metro: Activo | 6400imp/kW·h | |||||||
Reactivo | 6400imp/kvar·h | |||||||
Para 5(40) al metro: Activo | 600imp/kW·h | |||||||
Constante | Reactivo | 600imp/kvar·h | ||||||
Para 5(60) /15 (60) un metro: Activo | 400imp/kW·h | |||||||
Reactivo | 400imp/kvar·h | |||||||
Para 20(100) A | metro: | Activo | 300imp/kW·h | |||||
Reactivo | 300imp/kvar·h | |||||||
Anchura de pulso | (80±20) ms |
Error de reloj | ≤0.5 s/d | 0℃~+40℃: ±2ppm; | ||
-40℃~+85℃: ±3.5ppm | ||||
Frecuencia de reloj | 1Hz | |||
Vida de batería | 10 años | |||